800/1200/1500/2000 Lumen Gen 3 LED Adjustable Downlight Dimmer Compatibility for Use With: IC420L, TC420L, IC415L, IC412L, IC408L, IC408LR, TC412LR, IC420LSQ, TC420LSQ, IC415LSQ, IC412LSQ, IC408LSQ
DECDICATED 120V ONLY FIXTURES (-1)
Incandescent, Magnetic Low Voltage and Electronic Low Voltage Dimming
- Dimmable with the use of most forward and reverse phase dimmers
- Dimming range of 100% down to 5% or lower with a minimum load of one fixture; both dimming range and maximum rated load may vary depending on dimmer model
- See maximum load calculations below to identify max number of luminaires per dimmer.
Forward Phase
(Incandescent and Magnetic Low Voltage)
Example: Fixture Rating = 13W
Dimmer Rating = 600W
Equivalent Incandescent Load (EIL) = 50%
(600/13W) X 0.5 = 23 Fixtures per Dimmer
Manuf. | Product Family | Series | Type | Min Light (%) |
Lutron | Glyder | GLV* | MLV | 2 |
Lutron | Nova T | NTLV | MLV | 2 |
Lutron | Rotary | D | INC | 2 |
Lutron | Diva | DVLV* | MLV | 3 |
Lutron | Ceana | CNLV | MLV | 3 |
Lutron | Diva | DV | INC | 2 |
Lutron | Skylark | S | INC | 2 |
Lutron | Ariadni | AY | INC | 2 |
Lutron | Skylark | SLV* | MLV | 3 |
Lutron | Diva | DVCL | INC | 2 |
Lutron | Ariadni | AYCL | INC | 2 |
Lutron | Toggler | TGCL | INC | 2 |
Lutron | Lumea | LGCL | INC | 2 |
Lutron | Skylark Contour | CTCL | INC | 2 |
Lutron | RadioRA2 | RRD-10ND* | PHA | 2 |
* Aculux recommended dimmers
Reverse Phase
(Electronic Low Volatge)
Example: Fixture Rating = 13W
Dimmer Rating = 600W
Equivalent Incandescent Load (EIL) = 75%
(600/13W) X 0.75 = 34 Fixtures per Dimmer
Reverse Phase |
||||
Manuf. | Product Family | Series | Type | Min Light (%) |
Lutron | Maestro | MAELV* | ELV | 3 |
Lutron | Faedra | FAELV | ELV | 3 |
Lutron | Spacer | SPSELV | ELV | 3 |
Lutron | Nova T | NTELV | ELV | 3 |
Lutron | Diva | DVELV | ELV | 2 |
Lutron | Skylark | SELV | ELV | 2 |
Lutron | RadioRA2 | RRD-6NA* | PHA | 2 |
Lutron | Vizia | VPE06-1LX* | ELV | 2 |
Lutron | Illuminatech | IPE04* | ELV | 5 |
* Aculux recommended dimmers
Integrated Control Systems |
||||
Manuf. | Product Family | Series | Type | Min Light (%) |
Lutron | GrafikEye QS | PHPM-PA* | PHA | 1 |
Lutron | HomeWorks QS | PHPM-PA* | PHA | 1 |
Lutron | HomeWorks QS | HW-RPM-4A | PHA | 2 |
Lutron | LCP128 | PHPM-PA* | PHA | 1 |
Lutron | LCP128 | LP-RPM-4A | PHA | 1 |
Lutron | LP | PHPM-PA* | PHA | 1 |
Lutron | LP | LP-RPM-4A | PHA | 1 |
* Aculux recommended dimmers
UNIVERSAL 120-277V FIXTURES
0-10V Dimming (-U)
- Dimmable with the use of most 0-10V protocol dimmers
- Dimming range of 100% to 10%.
0-10 Dimming |
||||
Manuf. | Product Family | Series | Type | Min Light (%) |
Lutron | Diva | DVTV* | 0-10V | 10 |
Lutron | Nova | NFTV* | 0-10V | 10 |
Lutron | Nova T | NTFTV* | 0-10V | 10 |
Lutron | Illuminatech | IP710-DL* | 0-10V | 10 |
* Aculux recommended dimmers
Integrated Control Systems |
||||
Manuf. | Product Family | Series | Type | Min Light (%) |
Lutron | GrafikEye QS | GRX-TVI* | 0-10V | 10 |
Lutron | HomeWorks QS | GRX-TVI* | 0-10V | 10 |
Lutron | HomeWorks QS | GRX-TVM2* | 0-10V | 10 |
Lutron | LCP128 | GRX-TVI* | 0-10V | 10 |
Lutron | LCP128 | GRX-TVM2* | 0-10V | 10 |
Lutron | LP | GRX-TVM2* | 0-10V | 10 |
Lutron | RadioRA2 | LMJ-5T-DV-B | 0-10V | 10 |
Lutron | Energi Tripak | RMJ-5T-DV-B | 0-10V | 10 |
* Aculux recommended dimmers
DMX Dimming (-M)
- Compatible with ANSI+E1.11-2008R2013 (USITT DMX512-A) controller and system equipment.
DALI Dimming (-A)
- Compatible with IEC 62386-207 and IEC 62386-102 certified controller and system equipment.
Lutron HI-Lume A-Series Driver
120V-277V 3-Wire Fluorescent Controls and EcoSystem Digital Controls (-L)
- For a list of compatible dimmers, please reference Lutron’s Report Card for EcoSystem and 3-Wire Control dimming systems located at: https://cdn.shopify.com/s/files/1/0681/6625/4899/files/EcoSystem_3-wire_report_card.pdf
120V 2-Wire Forward Phase Controls (-D)
- For a list of compatible dimmers, please reference Lutron’s Report Card for 2-Wire Control dimming systems located at: https://cdn.shopify.com/s/files/1/0681/6625/4899/files/2-wire_fwd_phase_report_card.pdf